Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM05188
Parcel: 126210710

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T18CM05188
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2018 MARTIN BROWN FIRE REVIEW Reqs Change Per 2012 International Fire Code, residences in excess of 3600 square feet require a commercial fire flow. Owner has three options.
1) Do a flow test of the nearest hydrant and prove a flow of 2000 GPM at 20 psi (unlikely due to low pressures in the neighborhood)
2) Install fire sprinklers in the house.
3) Do not add any square footage to the house.
07/20/2018 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T18CM05188

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FLOOR PLANS:

1. Show compliance with R310.1 providing egress from the basement. The basement requires one operable emergency escape and rescue opening.

ELECTRICAL PLANS:

1. Panelboards may not be located in storage rooms, clothes closets or bathrooms or over steps of a stairway, E3405.4. Relocate panel "B".

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/23/2018 AVAUGHN1 OUT TO CUSTOMER Completed