Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T18CM05137
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/30/2019 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T18CM05137 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012 that remained in effect until 1/1/2019. Provide the code reference used for the design on the plans. GENERAL COMMENTS: 1. Provide consecutive sheet numbers on each construction drawing, R106.1.1. Include the HVAC duct layout sheet. 2. Each dwelling unit building requires a street address and a separate permit, R101.3. Show the address for this building on the plans. FLOOR PLANS: 1. Show porch roof structures with one-hour fire-resistive construction separating the units in compliance with IBC Table 721.1(2), or show a clear 3' fire separation distance determined from a line parallel with the building separation line (imaginary property line). This separation is required from ground to roof and from end to end of the porch roof. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
01/31/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. Put the required minimum lowest floor elevation (2486.1 FT NAVD 1988) on the floor plan. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/08/2019 | AVAUGHN1 | APPROVAL SHELF | Completed |
02/08/2019 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
02/08/2019 | AVAUGHN1 | REJECT SHELF | Completed |