Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM05106
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/05/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1 Ref; Plan Sheet E1.0. Designate a branch circuit and panel for the 2 receptacle in room # 114. #2 Locate new panel 'G' on the electrical floor plans. #3 Provide a complete panel schedule for panel 'D', and 'G' include panel size in ampacity. #4 Provide complete compliance with the 2012 IECC. Ref; 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Review Requirements. |
| 07/05/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. [Second comment: Provide structural calculations to verify that the proposed framework will safely support the water heater. Include fastening details.] [Initial comment: Provide architectural detail showing how to anchor water heater bracket to wall.] |
| 07/06/2018 | MARTIN BROWN | FIRE | REVIEW | Approved |