Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM05106
Parcel: 130130610

Address:
3635 E 34TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM05106
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1 Ref; Plan Sheet E1.0. Designate a branch circuit and panel for the 2 receptacle in room # 114.
#2 Locate new panel 'G' on the electrical floor plans.
#3 Provide a complete panel schedule for panel 'D', and 'G' include panel size in ampacity.
#4 Provide complete compliance with the 2012 IECC.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Review Requirements.
07/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not addressed. [Second comment: Provide structural calculations to verify that the proposed framework will safely support the water heater. Include fastening details.] [Initial comment: Provide architectural detail showing how to anchor water heater bracket to wall.]
07/06/2018 MARTIN BROWN FIRE REVIEW Approved