Review Details: COMMERCIAL - TI

Permit Number - T18CM05106
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Approved
07/03/2018 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/03/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1.Comment not resolved. If you want to connect the fixture drain of the drinking fountain to the vent of the mop sink, use a common vent, [Initial comment: Revise the venting configuration for P4 and P-5 in the partial waste & vent diagram: either show the fixtures as being common vented or provide two individual vents (using air admittance valves).]
2. Comment not resolved. State the mounting height for each drinking fountain. [Initial comment: One of the two drinking fountains is to be mounted with maximum a spout height of 36" AFF and the other with a spout height of 38-43" AFF. Reference: Section 602.4, ANSI/ICC A117.1-2009.]
3. Provide structural calculations to verify that the proposed framework will safely support the water heater. Include fastening details. [Initial comment: Provide architectural detail showing how to anchor water heater bracket to wall.]
07/05/2018 KROBLES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/05/2018 KROBLES1 FIRE REVIEW Needs Review