Permit Number: T18CM05106
Parcel: 130130610

Address:
3635 E 34TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05106
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2018 ALEXANDRA HINES ZONING REVIEW Approved
06/28/2018 AHINES2 ENGINEERING REVIEW Passed
06/29/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments.
#1 Refer to mechanical plans for the operation of the exhaust fans and revise electrical plan.
#2. Please indicate what is new and existing for power and lighting equipment and devices.
Ref: 2012 IBC sec 107.2.1, 2011 NEC .
06/29/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/29/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide framing details of all new walls that show anchorage to the floor and roof/ceiling.
2. Drinking fountains are required for persons in wheelchairs and standing use. Specify ADA drinking fountains.
3. Provide and exiting plan for the new office; specify the common path of egress travel and maximum travel distance from the office.
06/29/2018 ROBERT SHERRY WATER REVIEW Completed
06/29/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the venting configuration for P4 and P-5 in the partial waste & vent diagram: either show the fixtures as being common vented or provide two individual vents (using air admittance valves).
2. One of the two drinking fountains is to be mounted with maximum a spout height of 36" AFF and the other with a spout height of 38-43" AFF. Reference: Section 602.4, ANSI/ICC A117.1-2009.
3. What is P-7 (detail A/P1.1)?
4. Provide architectural detail showing how to anchor water heater bracket to wall.
07/03/2018 SVALENZ1 FIRE REVIEW Needs Review
07/03/2018 SVALENZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review