Permit Number: T18CM05098
Parcel: 122174520

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T18CM05098
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2018 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T18CM05098
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Update detail A/S-5.

PLUMBING PLANS:

1. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Increase pipe diameter or reduce the developed length.
2. Provide a gas (1,000 BTUh = 1 CFH) conversion coordinated with Southwest Gas. Update the Gas Schedule sheet P-2.

ELECTRICAL PLANS:

1. Show locations of each smoke alarm, R314. Smoke alarms are required both inside and outside each separate sleeping area, R314.3.2.
2. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
3. Revise the electrical load calculations following Table E3602.2 for sizing the dwelling load. The floor area shown on the calculations is not consistent with the areas shown on sheet C-1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2018 SVALENZ1 OUT TO CUSTOMER Completed