Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T18CM05094
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/02/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/03/2018 | FRODRIG2 | COMMUNICATIONS | REVIEW | Approved | LETTER SENT TO RECORDS |
| 07/16/2018 | GPERU1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/16/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/23/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 07/25/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T18CM05094 - New Cell Tower (Communications - 50' Mono-Elm Tower) Building Plan Review (1st Review) Sunset State Towers 2921 E. Fort Lowell Road TRANSMITTAL DATE: July 25, 2018 DUE DATE: July 30, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has done a review of the Mono-Elm plans and compared the building plans to the PDP. While the cursory review did yield an indication that the Mono-Elm Cell Tower plans are consistent with what has been approved through the Special Exception Process zoning cannot approve the plans at this time. 2. COMMENT: Zoning is requesting that the elevation drawings include a clear representation of the Mono-Elm. The elevation drawings submitted are very light and the elm tree is not visible. Revise the elevations drawings or include another sheet that clearly depicts the elm tree camouflage. 3. Zoning is willing to do an over the counter review and approval of the plans on the next submittal for compliance with the requested zoning changes. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Mono-Elm elevation Drawings |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/14/2018 | KROBLES1 | OUT TO CUSTOMER | Completed |