Permit Number: T18CM05086
Parcel: 13606002C

Address:
8800 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T18CM05086
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/31/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Coordinate the specifications for the restroom exhaust fan with the balancing data on the drawing.
2. Provide specifications for the programmable thermostats to show that they meet all of the requirements in Section C403.2.4, IECC 2012.
3. Show how an auxiliary or secondary condensate drain system will be provided. Reference: Section 307.2.3, IMC 2012.
08/13/2018 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/13/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Approved
08/13/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please revise the electrical plan so the replaced panel mark or label correlates with the one line diagram. Also the size and ratings don't match. Panel 'MPW3-1' is shown as a 100 amp panel. This panel cannot feed thru to feed a 200 amp panel.
Ref; 2012 IBC 107.2.1, 2011 NEC 408.4

Final Status

Task End Date Reviewer's Name Type of Review Description
08/13/2018 QJONES1 APPROVAL SHELF Completed
08/13/2018 QJONES1 OUT TO CUSTOMER Completed
08/13/2018 QJONES1 REJECT SHELF Completed