Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/31/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
07/31/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Coordinate the specifications for the restroom exhaust fan with the balancing data on the drawing. 2. Provide specifications for the programmable thermostats to show that they meet all of the requirements in Section C403.2.4, IECC 2012. 3. Show how an auxiliary or secondary condensate drain system will be provided. Reference: Section 307.2.3, IMC 2012. |
08/13/2018 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/13/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/13/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please revise the electrical plan so the replaced panel mark or label correlates with the one line diagram. Also the size and ratings don't match. Panel 'MPW3-1' is shown as a 100 amp panel. This panel cannot feed thru to feed a 200 amp panel. Ref; 2012 IBC 107.2.1, 2011 NEC 408.4 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/13/2018 | QJONES1 | APPROVAL SHELF | Completed |
08/13/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
08/13/2018 | QJONES1 | REJECT SHELF | Completed |