Permit Number: T18CM05086
Parcel: 13606002C

Address:
8800 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05086
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/28/2018 SVALENZ1 ZONING REVIEW Approved PER ELISA
06/28/2018 SVALENZ1 ENGINEERING REVIEW Passed PER ELISA
06/28/2018 MARTIN BROWN FIRE REVIEW Approved
06/29/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments.
#1. Assign panel designations along with the branch circuit or feeder numbers.
#2. Provide a line diagram for the electrical system. Include feeder, conduit, conductor, OCPD's sizes and types.
#3. Provide load calcs for the building service and panel 'A'.
Ref: 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal requirements.
06/29/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide specifications for the restroom exhaust fan.
2. Provide a sequence of operation for the exhaust fan.
3. Provide specifications for the programmable thermostats to show that they meet all of the requirements in Section C403.2.4, IECC 2012.
4. Provide the SEER for the proposed AC units; verify if an economizer is required. Reference: Section C403.3.1, IECC 2012.
5. Provide an auxiliary or secondary condensate drain system. Reference: Section 307.2.3, IMC 2012.
6. Provide ventilation for the restrooms and the corridor.
06/29/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. CS1 Provide minimum plumbing fixture calculations based on the total occupant load for compliance with IBC TABLE 2902.1
2. The class rooms are required to be accessible; specify existing compliance with IBC 1103.1
3. A4 Structural calculations are required for the new exterior stairway; or specify if struc. calcs. from fabricator is on deferred submittals. IBC 107.2.1
4. A4 The stair guard rail for the stairs and elevated platform is required to have rail spacing not to exceed a clear space of 4 inches. IBC 1013.2
5. A4 Specify a landing at the base of the stairs. IBC 1009.8
6. A1 Provide framing details of all partitions; specify anchorage method at floor and roof. IBC 107.2.1
7. Provide details of the acoustic tile installation. IBC 808.1
8. Specify distances and occupants served on exit egress paths. IBC 107.2.1
06/29/2018 ROBERT SHERRY WATER REVIEW Completed
06/29/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a drinking fountain.
07/31/2018 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review