Permit Number: T18CM05064
Parcel: 13225069G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM05064
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1 (Cee Purlin); Structural Calculations (Sheet 7): The calculations indicate a 10 x 3.5 x 12 ga. roof purlin, while the detail indicates a 10 x 3.5 x 14 ga. purlin. Please coordinate.
2. Sheet S1; Cee Purlin: The purlin is called out as a 10 x 3.5, but the section shows a 10 x 2.5. Please coordinate.
3. Sheet S1 (General Structural Notes); Structural Calculations (Sheet 23): The calculations indicate the required connection of the roof deck to the purlins, but that information was not located on the drawings. Please provide.
4. Sheet S3 (Beam to Column Detail); Structural Calculations (Sheet 23): The calculations indicate 3/8" x 2" x 14" side plates, while the detail indicates side plates 3/8" x 5" x 5". Please coordinate.
5. General: Please provide written responses to all review comments.