Permit Number: T18CM05054
Parcel: 13005302A

Address:
2403 S MARTIN AV

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM05054
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2018 MARTIN BROWN FIRE REVIEW Approved
07/03/2018 FRODRIG2 COMMUNICATIONS REVIEW Completed LETTER SENT TO RECORDS
07/03/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. The structural calculations package submitted for this project does not fit the site location or Carrier Site name that is on the plan documents. Submit proper calculations for this project. IBC 107.2.1
2. Structural calculations are required for the structural modifications to the tower, please submit. IBC 1704.2
3. Provide a listing of special inspections associated with this project. IBC 1704.2.3
4. The call out for detail 4/A-3 on sheet A-3 says NOT USED, but is shown as a detail. Revise the call out to the proper reference. IBC 107.2.1
07/05/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Approved
07/05/2018 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/06/2018 KROBLES1 OUT TO CUSTOMER Completed