Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM05053
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/05/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. No compliance or response to the previous electrical plan review comment. It was requested to provide load calcs for the new 200 amp service and panels '4818' and Ex panel '4818 A'. NEC art 220. #2. To help clarify or justify the plan reviewer's request, the following changes were noted from the existing installation to the new or modified installation; (a) The existing 600 amp (200 + 400 ) service was replaced with a 200 amp service. (b) The existing panel 4818 was replaced with a new 200 amp panel with the following existing loads that are not shown in the existing loads, or existing panels, ( 4 AC Units ). Plus the existing panel '4818 A', plus the saw and receptacle. (c) There are no load calcs for branch circuits or total loads, or balanced loads as required per NEC art 220 and the City of Tucson Commercial Plan Submittal Requirements. This information is required to determine the installation meets the requirements of the 2011 NEC. The NEC is enforced for the safeguarding of persons and property from the hazards arising from the use of electricity. NEC 90.1. 90.4 Ref; 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements. |