Permit Number: T18CM05043
Parcel: 137070570

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM05043
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/29/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide written response.
After clarification of the method for the proposed load side PV Interconnection, and further review, it was determined by the electrical plan reviewer, that the load side interconnection would be in violation of NEC art 705.12D(1).