Permit Number: T18CM05043
Parcel: 137070570

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM05043
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet PV1.0; Project Information: Please indicate on the sheet the occupancy classification and the construction type for this project.
2. Sheet PV2.0; Site Plan: Please provide dimensions on the plan indicating the distance from the new structures to property lines, existing buildings/structures, and the other new canopy structures.
3. Special Inspection Certificate: Under the "Special Inspector" heading, please indicate the name of the ICC certified individual for each special inspection.
07/16/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet PV 4.0, PV 4.5. There is a note by the PV interconnection on the three line diagram that refers to a detail on plan sheet PV4.5 pertaining to the double lugs used to terminate the PV output conductors. No detail was found. Please clarify.
#2. Provide more detail for the tap into the existing exterior lighting branch circuit. Wiring methods.
Ref; 2012 IBC sec 107.2.1, 2011 NEC.
08/29/2018 TWEIDEM1 OIP REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/10/2018 TWEIDEM1 OUT TO CUSTOMER Completed