Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T18CM04998
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/05/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/06/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the site plan referenced on sheet P1.0 showing the route of the building sewer to the public sewer. Reference: Section 107.2.1, IBC 2012. 2. Specify the material of construction for the building sewer. Reference: Section 702.3, IPC 2012. 3. Show the location of all cleanouts for the building sewer. Reference: Section 703.5, IPC 2012. |
| 07/06/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the building envelope using COMcheck. Reference: Sections C101.3, C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2012. 2. Provide heating and cooling load calculations, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson. |
| 07/06/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the site plan referenced on sheet P1.0 showing the location of the water meter, reduced pressure backflow assembly and the route of the water service to the building. Specify the material of construction for the water service pipe. Reference: Section 107.2.1, IBC 2012. |
| 07/13/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0; Floor Plan Keynotes: Note 1 indicates a pre-manufactured aluminum canopy system. Please add to this note (or add note to Sheet TS1), indicating this canopy will be a deferred submittal and must follow the requirements of the IBC Sections 107.3.4 and 107.3.4.1. 2. Sheets A2.0 and A2.1; Exterior Elevation Keynotes: Note 3 should be modified per Comment 1. 3. Sheet A4.0; Building Section 1: A reference is made to Detail 1/A4.0 at the right side of this section. Please revise that detail reference. 4. Sheet A4.1; Wall Section Keynotes: Note 14 should be modified per Comment 1. 5. Sheet A6.1; Wall Section 3: A reference is made to a detail on Sheet A2.1. Please revise that detail reference. 6. Sheet S1.0 (Foundation Plan); Structural Calculations (Sheet 14): At the west end of the building, two 4 foot build-outs indicate SW4 on the north-south walls, while the calculations indicate shear walls on all four sides. Please verify. 7. Sheet S1.0 (Foundation Plan); Structural Calculations (Sheet 14): At the northwest corner area of the building, a free standing build-out indicates SW4 only on the north-south wall (on the west side of the build-out), while the calculations indicate shear walls on all four sides. Please verify. 8. Sheet S1.0; Column Schedule: Please provide structural calculations for the steel tube column design. 9. Sheets S1.1 and S1.2: Please provide structural calculations for the various signs and light pole indicated on these sheets. 10. Sheets S1.1 and S1.2: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise this sheet. 11. Sheet S2.0 (Roof Framing Plan); Structural Calculations (Sheet 5): The calculations indicate J-2 as RED-165(14") at 16 inches o.c., while the drawings indicate joist J-2 as RED-165(11 7/8") at 24 inches o.c.. Please coordinate. 12. Sheet S2.0 (Roof Framing Plan); Structural Calculations (Sheet 5): The calculations indicate J-3 as 600-250-33 at 24 inches o.c., while the drawings indicate joist J-4 as 2x8 at 24 inches o.c. Please coordinate. 13. Sheet S2.0 (Joist Schedule); Structural Calculations: The joist schedule includes wood joists (J-3 and J-4), while there are no calculations for wood joists. Please verify and provide. 14. Sheet S2.0; Details: Please indicate all detail references on the Roof Framing Plan. 15. Sheet S2.0; Roof Framing Plan: A detail reference 3/S1.0 is indicated at the east wall of the electrical room. Please revise that detail reference. 16. Sheet S2.0: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise this sheet. 17. General: Please provide the Special Inspection Certificate for this project. 18. General: Please provide written responses to all review comments. |
| 07/17/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/23/2018 | SVALENZ1 | ZONING | REVIEW | Needs Review | |
| 07/23/2018 | SVALENZ1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/23/2018 | SVALENZ1 | OUT TO CUSTOMER | Completed |