Permit Number: T18CM04926
Parcel: 13316047A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM04926
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/22/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide a mechanical plan that shows how the new kitchen complies with the requiremnents of Sections 403, 506, 507, and 508, IMC 2012.
06/22/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/22/2018 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the size and serial number of the water meter for this building and determine the demand served by the meter.
2. Provide the size, type, and location of the backflow prevention assembly associated with the water meter.
06/22/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/22/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide plumbing plans for the revised kitchen.
06/27/2018 MARTIN BROWN FIRE REVIEW Approved
06/28/2018 ALEXANDRA HINES ZONING REVIEW Approved
06/28/2018 AHINES2 ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/18/2018 QJONES1 APPROVAL SHELF Completed
07/18/2018 QJONES1 OUT TO CUSTOMER Completed
07/18/2018 QJONES1 REJECT SHELF Completed