Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM04926
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/22/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/22/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide a mechanical plan that shows how the new kitchen complies with the requiremnents of Sections 403, 506, 507, and 508, IMC 2012. |
06/22/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/22/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Provide the size and serial number of the water meter for this building and determine the demand served by the meter. 2. Provide the size, type, and location of the backflow prevention assembly associated with the water meter. |
06/22/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/22/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide plumbing plans for the revised kitchen. |
06/27/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/28/2018 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
06/28/2018 | AHINES2 | ENGINEERING | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/18/2018 | QJONES1 | APPROVAL SHELF | Completed |
07/18/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
07/18/2018 | QJONES1 | REJECT SHELF | Completed |