Permit Number: T18CM04912
Parcel: 112042700

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM04912
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the applicability of detail 204 to the installation of the natural gas service to the water heater.
2. The water heater schedule calls for a hot-water recirculation system, detail 201 specifies a water heater "w/o recirculation", and detail 201 also notes a "circuit-setter balanced to XX GPM". Clarify what is to be installed.
3. Verify that the Proset Trap guard is listed for use in a floor sink. Note that the floor sink under a 3-compartment sink is generally not subject to the loss of the trap seal due to evaporation. Reference: Section 1002.4, IPC 2012, as amended by the City of Tucson.
4. Coordinate the location of the floor sink (kitchen equipment #7) with the architect.
07/05/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change What is the source of the 475 CFM of make-up air for the exhaust hood that is not being supplied by the evaporative cooler?
07/13/2018 SVALENZ1 ZONING REVIEW Needs Review
07/13/2018 SVALENZ1 ELECTRICAL-COMMERCIAL REVIEW Needs Review