Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM04912
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/05/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the applicability of detail 204 to the installation of the natural gas service to the water heater. 2. The water heater schedule calls for a hot-water recirculation system, detail 201 specifies a water heater "w/o recirculation", and detail 201 also notes a "circuit-setter balanced to XX GPM". Clarify what is to be installed. 3. Verify that the Proset Trap guard is listed for use in a floor sink. Note that the floor sink under a 3-compartment sink is generally not subject to the loss of the trap seal due to evaporation. Reference: Section 1002.4, IPC 2012, as amended by the City of Tucson. 4. Coordinate the location of the floor sink (kitchen equipment #7) with the architect. |
07/05/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | What is the source of the 475 CFM of make-up air for the exhaust hood that is not being supplied by the evaporative cooler? |
07/13/2018 | SVALENZ1 | ZONING | REVIEW | Needs Review | |
07/13/2018 | SVALENZ1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |