Permit Number: T18CM04909
Parcel: 138220180

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM04909
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2018 MARTIN BROWN FIRE REVIEW Approved
07/10/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change PV3.0. The clouded area of the one-line drawing shows that the conductors from SC1, SC2 are to be copper; the SUMMARY FEEDER SCHEDULE does not show copper to be used from the inverters to the AC combiner panel. Please correct the type of cable to be used.
PV4.0 The note referencing the bonding jumper to the canopy per detail on PV4.5 is to a plan sheet that is not in the permit documents. The electrical detail sheet PV4.5 is not contained in the plan set; please submit sheet.
PV4.0 Indicate the size of the bonding jumper from the neutral lug to the CT CABINET.
NOTICE FOR INSPECTOR: The 3-line drawing shows a supply-side connection for the photovoltaic system. A field inspection by an NRTL to RE-LIST the Sevice equipment may be necessary after the supply side tap is performed.
07/10/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2018 AVAUGHN1 REJECT SHELF Completed