Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM04909
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/26/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/10/2018 | GPERU1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | PV3.0. The clouded area of the one-line drawing shows that the conductors from SC1, SC2 are to be copper; the SUMMARY FEEDER SCHEDULE does not show copper to be used from the inverters to the AC combiner panel. Please correct the type of cable to be used. PV4.0 The note referencing the bonding jumper to the canopy per detail on PV4.5 is to a plan sheet that is not in the permit documents. The electrical detail sheet PV4.5 is not contained in the plan set; please submit sheet. PV4.0 Indicate the size of the bonding jumper from the neutral lug to the CT CABINET. NOTICE FOR INSPECTOR: The 3-line drawing shows a supply-side connection for the photovoltaic system. A field inspection by an NRTL to RE-LIST the Sevice equipment may be necessary after the supply side tap is performed. |
07/10/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/09/2018 | AVAUGHN1 | REJECT SHELF | Completed |