Permit Number: T18CM04907
Parcel: 11005014C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM04907
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/22/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/22/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/22/2018 JVINCEN1 FIRE REVIEW Approved
06/22/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/22/2018 ROBERT SHERRY WATER REVIEW Completed
06/22/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide hot water to the 3-compartment sink. Reference: Section 607.1, IPC 2012.
2. Owner-supplied plumbing fixtures shall be third-party listed (e.g. NSF)reference: Section 303.4, IPC 2012.
3. Explain how the trap guard (detail 202) will be used in the specified floor sink without causing splashing or flooding. Reference: Section 802.3.1, IPC 2012.
06/26/2018 MMORENO1 ENGINEERING REVIEW Passed
06/26/2018 MMORENO1 ZONING REVIEW Approved