Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM04907
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/22/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/22/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
06/22/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/22/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
06/22/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/22/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
06/22/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide hot water to the 3-compartment sink. Reference: Section 607.1, IPC 2012. 2. Owner-supplied plumbing fixtures shall be third-party listed (e.g. NSF)reference: Section 303.4, IPC 2012. 3. Explain how the trap guard (detail 202) will be used in the specified floor sink without causing splashing or flooding. Reference: Section 802.3.1, IPC 2012. |
06/26/2018 | MMORENO1 | ENGINEERING | REVIEW | Passed | |
06/26/2018 | MMORENO1 | ZONING | REVIEW | Approved |