Permit Number: T18CM04855
Parcel: 133200250

Review Status: Active

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T18CM04855
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2018 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
07/18/2018 MARTIN BROWN FIRE REVIEW Reqs Change This residence will have a "fire-flow calculation area greater than 3,600 sq. ft.: therefore this house will require a residential sprinkler system unless the fire flow in the nearest hydrant is a minimum of 1,750 GPM for 2 hours duration at 20 psi residual pressure. Have a licensed fire sprinkler contractor perform a flow test. Provide notes on plan regarding verification of fire flow and proximity of hydrant or intent to install a fire sprinkler system. If a system will be installed, residential or quick response sprinklers shall be used. The sprinkler system may be connected to the domestic water supply, provided the required design density can be met. Be advised that Tucson Water will not allow a residential sprinkler system to be supplied by a 5/8" meter. A minimum of ¾" meter will be required by Tucson Water. Residential fire sprinkler system shall be installed in accordance with the 2018 IFC and NFPA 13D.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/22/2018 ANY REJECT SHELF RECEIVED