Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM04799
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/25/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/09/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet PV2.0; Site Plan: Please provide dimensions on the plan indicating the distance from the new structure to property lines and to existing buildings/structures. 2. Special Inspection Certificate: Under the "Special Inspector" heading, please indicate the name of the ICC certified individual for each special inspection. 3. Sheet PV1.0: Please indicate on the sheet the occupancy classification and construction type for this project. |
| 07/11/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide more detail as how the existing light pole wiring is to be intercepted and re-routed to the new under canopy lighting. #2. Provide for an ac disconnect to be installed at the inverter location. Per NEC definition art 100, Within site is within site but not to exceed a distance of 50 feet. Per scale the distance between the inverter and the transformer disconnect exceeds 50 feet. Ref; 2012 IBC section 107.2.1, 2011 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/09/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |