Permit Number: T18CM04799
Parcel: 140280230

Address:
2238 E GINTER RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM04799
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2018 MARTIN BROWN FIRE REVIEW Approved
07/09/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet PV2.0; Site Plan: Please provide dimensions on the plan indicating the distance from the new structure to property lines and to existing buildings/structures.
2. Special Inspection Certificate: Under the "Special Inspector" heading, please indicate the name of the ICC certified individual for each special inspection.
3. Sheet PV1.0: Please indicate on the sheet the occupancy classification and construction type for this project.
07/11/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide more detail as how the existing light pole wiring is to be intercepted and re-routed to the new under canopy lighting.
#2. Provide for an ac disconnect to be installed at the inverter location. Per NEC definition art 100, Within site is within site but not to exceed a distance of 50 feet. Per scale the distance between the inverter and the transformer disconnect exceeds 50 feet.
Ref; 2012 IBC section 107.2.1, 2011 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2018 AVAUGHN1 OUT TO CUSTOMER Completed