Permit Number: T18CM04774
Parcel: 12101262G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM04774
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2018 MCASTRO2 ZONING REVIEW Approved
06/19/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide the sequence of operation for the restroom exhaust fan.
06/19/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide specifications for the new plumbing fixtures.
2. Provide tempered water to the lavatories using mixing valves listed to ASSE 1070.
3. Provide lavatory faucets that dispence 0.25 gallons per cycle that have a cycle that lasts at least 10-seconds.
06/19/2018 MCASTRO2 ENGINEERING REVIEW Passed
06/19/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide wall framing details of cross sections; show mechanical connection of walls at the roof and floor.
2. Provide enlarged restroom floor plans and show required maneuvering spaces at the water closet and lavatories. The water closet is required to have 60 inches of clear space.
3. Provide wall elevations of plumbing fixtures, grap bars and dispensers; show heights and dimensions.
4. Specify an accessible route for the mens restroom.
06/19/2018 ROBERT SHERRY WATER REVIEW Completed
06/20/2018 LPEREZ2 ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/20/2018 LPEREZ2 FIRE REVIEW Needs Review
06/20/2018 LPEREZ2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review