Review Details: COMMERCIAL - TI
Permit Number - T18CM04740
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/19/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Please provide the types of occupancies for the existing temant spaces within the building. 2. For non-separated use calculations the most restrictive occupancy must be used for the base allowable area. Provide allowable area calculations using the most restrictive occupancy. 3. Label all required exits from the tenant space. 4. Provide a door schedule and include hardwate types. 5. Provide a wall schedule for all new wall installations. 6. Provide construction details for all new wall construction; detail connections at the roof and floor. 7. Access to restroom facilities is required for the tenant space; facilities must be under the same management as the tenant space. 8. Provide dimensions on the floor plan of the TI, 9. The classificatiion for the tenant improvement is listed as a storage use (S-2); provide a description of the types of materials or stock that will be stored. 10. Provide minimum plumbing fixture requirements for the T.I. 11. Provide a list of interior finish materials. 12. Specify the types of walls separating tenant spaces. |
| 06/19/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide a mechanical design (e.g. ventilation, refrigeration equipment, condensate drainage). |
| 06/19/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/19/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Provide the size, serial nimber, and the demand served by the existing water meter. 2. Provide the size and type of backflow preventer associated with the water meter. |
| 06/19/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/26/2018 | SVALENZ1 | ENGINEERING | REVIEW | Needs Review | |
| 06/26/2018 | SVALENZ1 | ZONING | REVIEW | Needs Review | |
| 06/26/2018 | SVALENZ1 | FIRE | REVIEW | Needs Review | |
| 06/26/2018 | SVALENZ1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |