Permit Number: T18CM04696
Parcel: 10701030A

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T18CM04696
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2018 ANY ZONING REVIEW Active
08/07/2018 MARTIN BROWN FIRE REVIEW Approved
08/07/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Specify GFCI outlets in the kitchen.
2. Specify GFCI outlets in the bathrooms.
3. Smoke detectors must be hardwired to the electrical service; provide circuit and panel designation.
4. All general purpose outlets must be ARC FAULT protected and tamper-proof.
5. The electrical outlet spacing exceeds maximum allowable by code; an outlet must be located not more than 6 ft. from doors and windows and not more than 12 ft. on center along wall sections.
6. Provide a panel schedule with type and circuit designations; indicate all branch circuits to altered space.
7. Provide load calculations for new work and specify location were service is located.
8. Specify the branch circuit size and rating to the water heater; show a disconnect at the water heater location.
9. Provide an electrical plan for the HVAC.
10. Indicate the branch circuit rating and over current rating for the new stove.
08/07/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/07/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/08/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide ventilation for the apartment.
2. Provide exhaust for the range.
08/08/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Clarify the waste and vent installation for the new sink.
08/08/2018 ROBERT SHERRY WATER REVIEW Reqs Change Verify the presence of a reduced pressure backflow preventer at the water meter serving this building.
10/15/2018 JOHN VAN WINKLE ENGINEERING REVIEW Approved