Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - TI
Permit Number - T18CM04696
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/15/2018 | ANY | ZONING | REVIEW | Active | |
08/07/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/07/2018 | GPERU1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Specify GFCI outlets in the kitchen. 2. Specify GFCI outlets in the bathrooms. 3. Smoke detectors must be hardwired to the electrical service; provide circuit and panel designation. 4. All general purpose outlets must be ARC FAULT protected and tamper-proof. 5. The electrical outlet spacing exceeds maximum allowable by code; an outlet must be located not more than 6 ft. from doors and windows and not more than 12 ft. on center along wall sections. 6. Provide a panel schedule with type and circuit designations; indicate all branch circuits to altered space. 7. Provide load calculations for new work and specify location were service is located. 8. Specify the branch circuit size and rating to the water heater; show a disconnect at the water heater location. 9. Provide an electrical plan for the HVAC. 10. Indicate the branch circuit rating and over current rating for the new stove. |
08/07/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/07/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/08/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide ventilation for the apartment. 2. Provide exhaust for the range. |
08/08/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Clarify the waste and vent installation for the new sink. |
08/08/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Verify the presence of a reduced pressure backflow preventer at the water meter serving this building. |
10/15/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved |