Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2018 STEVE SHIELDS ZONING REVIEW Approved
06/15/2018 SSHIELD1 ENGINEERING REVIEW Passed
06/15/2018 JVINCEN1 FIRE REVIEW Approved
06/19/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/19/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide ventilation for the changing room. Reference: Section 403.3, IMC 2012
06/19/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. The proper classification for the TI would be an 'M' occupancy for retail use.
2. Separate restroom facilities would be required for each sex when the occupancy is over 15 if this is classified as a 'B' occupancy.
3. The tenant space requires a drinking fountain or a point of use despensing station located in an accessible location. The use of a restaurant for required drinking fountain is not allowed because it is under different ownership or management and could be rendered inaccessible.
06/19/2018 ROBERT SHERRY WATER REVIEW Completed
06/19/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review Provide a drinking fountain. Reference: Section 2902, IBC 2012.