Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM04652
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/15/2018 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/15/2018 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 06/15/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 06/19/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/19/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide ventilation for the changing room. Reference: Section 403.3, IMC 2012 |
| 06/19/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. The proper classification for the TI would be an 'M' occupancy for retail use. 2. Separate restroom facilities would be required for each sex when the occupancy is over 15 if this is classified as a 'B' occupancy. 3. The tenant space requires a drinking fountain or a point of use despensing station located in an accessible location. The use of a restaurant for required drinking fountain is not allowed because it is under different ownership or management and could be rendered inaccessible. |
| 06/19/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/19/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | Provide a drinking fountain. Reference: Section 2902, IBC 2012. |
| 06/21/2018 | LPEREZ2 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |