Permit Number: T18CM04501
Parcel: 12709011M

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM04501
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/22/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/22/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change Please revisit the first review comments and verify all comments are addressed and revised as required.
1. Sheet X1.0 (Title); Sheet X1.0 (Location Plan): The Location Plan indicates Suite #201, while the Title indicates Suite 215. Please coordinate.
2. Sheet X1.0 (Location Plan); Sheet A1.0 (Reference Floor Plan): The Location Plan indicates Suite #201, while the Floor Plan indicates 100 series room identifications. Please verify.
3. Sheet A1.0; Partition B: The top of the partition should extend to the deck or be braced. Please verify and add detail as required.
4. Sheet A1.0; Partition C: The top of this partition must have braces indicated. Please provide detail.
5. Sheet A1.0; Partition C: The detail at the top of the storefront references 2/A2. Please revise that reference.
6. Sheet A4.0; Room Finish Schedule: Revise the Room Marks as required (this is second floor).
7. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/27/2018 QJONES1 APPROVAL SHELF Completed
06/27/2018 QJONES1 OUT TO CUSTOMER Completed
06/27/2018 QJONES1 REJECT SHELF Completed