Permit Number: T18CM04501
Parcel: 12709011M

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T18CM04501
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2018 EHAMBLI1 ZONING REVIEW Approved
06/11/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/11/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a complete panel schedule for panel '2L'.
Ref; 2012 IBC sec 107.2.1, 2011 NEC art. 408.4
06/11/2018 JOHN VAN WINKLE ENGINEERING REVIEW Passed
06/11/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet X1.0 (Title); Sheet X1.0 (Location Plan): The Location Plan indicates Suite #201, while the Title indicates Suite 215. Please coordinate.
2. Sheet X1.0 (Location Plan); Sheet A1.0 (Reference Floor Plan): The Location Plan indicates Suite #201, while the Floor Plan indicates 100 series room identifications. Please verify.
3. Sheet A1.0; Partition B: The top of the partition should extend to the deck or be braced. Please verify and add detail as required.
4. Sheet A1.0; Partition C: The top of this partition must have braces indicated. Please provide detail.
5. Sheet A1.0; Partition C: The detail at the top of the storefront references 2/A2. Please revise that reference.
6. Sheet A4.0; Room Finish Schedule: Revise the Room Marks as required (this is second floor).
7. General: Please provide written responses to all review comments.
06/11/2018 ROBERT SHERRY WATER REVIEW Completed
06/11/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Reprint sheet P3.1
06/11/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/12/2018 MARTIN BROWN FIRE REVIEW Approved