Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM04500
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/11/2018 | EHAMBLI1 | ZONING | REVIEW | Approved | |
06/11/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify what is happening to the existing cooling-only terminal unit (Keynote #9); it appears that all of the supply diffusers are being removed from the ternminal unit. 2. Clarify why one of the two instances of keynote #7 is connected to a supply diffuser. |
06/11/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
06/11/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
06/11/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet X1.0 (Title); Sheet X1.0 (Location Plan): The Location Plan indicates Suite #201, while the Sheet Title indicates #205. Please coordinate. 2. Sheet X1.0 (Location Plan); Sheet A1.0 (Reference Floor Plan): The Location Plan indicates Suite #201, while the Floor Plan indicates 100 series room identifications. Please verify. 3. Sheet A2.0; Room Finish Schedule: Revise the Room Mark as required (this is second floor). 4. General: Please provide written responses to all review comments. |
06/11/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
06/11/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
06/12/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
06/22/2018 | SVALENZ1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |