Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM04500
Parcel: 12709011M

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM04500
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2018 EHAMBLI1 ZONING REVIEW Approved
06/11/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify what is happening to the existing cooling-only terminal unit (Keynote #9); it appears that all of the supply diffusers are being removed from the ternminal unit.
2. Clarify why one of the two instances of keynote #7 is connected to a supply diffuser.
06/11/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/11/2018 JOHN VAN WINKLE ENGINEERING REVIEW Passed
06/11/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet X1.0 (Title); Sheet X1.0 (Location Plan): The Location Plan indicates Suite #201, while the Sheet Title indicates #205. Please coordinate.
2. Sheet X1.0 (Location Plan); Sheet A1.0 (Reference Floor Plan): The Location Plan indicates Suite #201, while the Floor Plan indicates 100 series room identifications. Please verify.
3. Sheet A2.0; Room Finish Schedule: Revise the Room Mark as required (this is second floor).
4. General: Please provide written responses to all review comments.
06/11/2018 ROBERT SHERRY WATER REVIEW Completed
06/11/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/12/2018 MARTIN BROWN FIRE REVIEW Approved
06/22/2018 SVALENZ1 ELECTRICAL-COMMERCIAL REVIEW Needs Review