Permit Number: T18CM04499
Parcel: 12709011M

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM04499
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change Please revisit the first review comments and verify all comments are addressed and revised as required.
1. Sheet X1.0 (Location Plan); Sheet A1.0 (Floor Plan): The Location Plan indicates Suite #201, while the Floor Plan indicates 100 series room identifications. Please verify.
2. Sheet A1.0; Interior Partition A: The top of this partition must have braces indicated. Please provide detail.
3. Sheet A3.0; Roof Finish Schedule: Revise the room marks as required (this is second floor).
4. General: Please provide written responses to all review comments.
06/22/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved