Permit Number: T18CM04494
Parcel: 11918036A

Address:
600 W AJO WY

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM04494
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2018 ALEXANDRA HINES ZONING REVIEW Approved
06/12/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012.
2. Provide a work platform for the exhaust fan per Section 306.5.1, IMC 2012.
3. Provide a Type II hood over the hot table. Reference: Section 507.2.2, IMC 2012.
4. Clarify the balancing requirements for the make-up air (i.e. where does the required additional 88 CFM come from?). Note that the supplied shop drawings have a different air flow rate for the make-up air.
06/12/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/12/2018 KROBLES1 ENGINEERING REVIEW Passed
06/12/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet g1.0; Code Review: Please revise the accessibility code to the 2009 ICC/ANSI A117.1.
2. Sheet S1.0; Plan and Details: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
3. Sheets FS3.0, FS3.1, FS3.2, and FS3.3; Notes: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
4. General: Please provide written responses to all review comments.
06/12/2018 ROBERT SHERRY WATER REVIEW Completed
06/12/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/12/2018 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/22/2018 ARUIZ1 FIRE REVIEW Needs Review