Permit Number: T18CM04426
Parcel: 13324010C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM04426
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/07/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the size of the dryer exhaust vent. Reference: Section 504.6.1, IMC 2012.
2. Provide a permanent label showing the total equivalent length of the installed dryer exhaust vent. Reference: section 504.6.5, IMC 2012.
3. Provide cooling/heating load calculations justifying the AC units being installed.
4. Provide a mechanical COMcheck demonstrating that the new AC units comply with the current energy code.
5. Provide makeup air for the dryer. Reference: Section 504.5, IMC 2012.
06/07/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/07/2018 ROBERT SHERRY WATER REVIEW Completed
06/07/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Project Data: Please indicate the occupant load on the drawings for this new unit.
2. Sheet A2.0; Wall Legend: The new wall indicates to see Detail 5/A4.0. Please revise the detail reference.
3. Sheet A4.0; Detail 4: If this is for new door lintels, please indicate on Detail 9 that this lintel is for existing and new steel lintels.
4. General: Please provide written responses to all review comments.
06/07/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Where is the hot water source located? If the source is greater than 50-feet from the loads, revise the design to reduce the effective pipe length or add heat tracing.. Reference: Section 607.2, IPC 2012.
3. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. clotheswasher). Reference: Section 604.9, IPC 2012.
06/08/2018 EHAMBLI1 ENGINEERING REVIEW Passed
06/08/2018 EHAMBLI1 ZONING REVIEW Approved
06/08/2018 MARTIN BROWN FIRE REVIEW Approved