Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM04424
Parcel: 13324010C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM04424
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/07/2018 ROBERT SHERRY WATER REVIEW Completed
06/07/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/07/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Project Data: Under "Building Area To Be Modified", a note indicates 'No Fire Sprinkler'. Under "Existing Fire Protection", a note indicates 'Existing Fire Sprinkler System'. Please coordinate.
2. Sheet A1.0; Project Data: Please indicate the occupant load on the drawings for this space.
3. Sheets A3.0 and A4.0 (Floor Plan); Sheet A7.0 (Sections): The sections all reference 1, 2, 3, or 4 on Sheets A3.0 and A4.0, while the sections on Sheet A7.0 indicate A, B, C, etc. Please coordinate.
4. Sheet A5.0; New Entry: Please provide structural calculations for the new entry framing and foundation design. Include general notes on the drawing for material strengths, design loads, etc.
5. Sheet A8.0; Sections: Please provide structural calculations for the masonry wall/column designs.
6. Sheet A9.0; Details 7 and 8: Is this an existing lintel or a new lintel at the new window opening? Please verify and revise the titles as required.
7. Sheet A10.0; Elevation 9: Per the ICC/ANSI Section 904.3.1, the accessible portion of the counter must be a minimum of 36" in length. Please revise the plan.
8. General: Please provide written responses to all review comments.
06/08/2018 EHAMBLI1 ENGINEERING REVIEW Passed
06/08/2018 EHAMBLI1 ZONING REVIEW Approved
06/08/2018 MARTIN BROWN FIRE REVIEW Approved
08/27/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. (Note: two different faucets are specified for the relocated lavatory.) Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
08/27/2018 AVAUGHN1 MECHANICAL-COMMERCIAL REVIEW Passed PASSED- PER RWS