Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM04424
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/07/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/07/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/07/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/07/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0; Project Data: Under "Building Area To Be Modified", a note indicates 'No Fire Sprinkler'. Under "Existing Fire Protection", a note indicates 'Existing Fire Sprinkler System'. Please coordinate. 2. Sheet A1.0; Project Data: Please indicate the occupant load on the drawings for this space. 3. Sheets A3.0 and A4.0 (Floor Plan); Sheet A7.0 (Sections): The sections all reference 1, 2, 3, or 4 on Sheets A3.0 and A4.0, while the sections on Sheet A7.0 indicate A, B, C, etc. Please coordinate. 4. Sheet A5.0; New Entry: Please provide structural calculations for the new entry framing and foundation design. Include general notes on the drawing for material strengths, design loads, etc. 5. Sheet A8.0; Sections: Please provide structural calculations for the masonry wall/column designs. 6. Sheet A9.0; Details 7 and 8: Is this an existing lintel or a new lintel at the new window opening? Please verify and revise the titles as required. 7. Sheet A10.0; Elevation 9: Per the ICC/ANSI Section 904.3.1, the accessible portion of the counter must be a minimum of 36" in length. Please revise the plan. 8. General: Please provide written responses to all review comments. |
| 06/08/2018 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
| 06/08/2018 | EHAMBLI1 | ZONING | REVIEW | Approved | |
| 06/08/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/27/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. (Note: two different faucets are specified for the relocated lavatory.) Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. |
| 08/27/2018 | AVAUGHN1 | MECHANICAL-COMMERCIAL | REVIEW | Passed | PASSED- PER RWS |