Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM04423
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/19/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/27/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0 (Site Plan); Sheet A3.0 (Floor Plan): Per the IBC Section 705.3, an imaginary line must be located between the new and existing buildings on a common lot if we are approaching this project as a separated occupancy. The distance from the new building or existing building to that imaginary line must meet the separation distance requirements of the IBC Table 602. If the buildings are closer than those values listed in Table 602, the exterior wall and opening protection must meet the criteria of Sections 705.5 and 705.8. It appears the west wall of the addition may be closer (15'-0" indicated on Sheet A1.0) than allowed. Please verify. 2. Sheet A3.0; Floor Plan: Per the IBC Section 1108.2.9.1, at least 5% of the dining surfaces for seating and standing spaces shall be accessible and located on an accessible route. Please indicate those accessible surfaces and seating locations in the dining area. In addition, please provide the accessible seating calculation on this sheet. 3. Sheet A3.0; Floor Plan: Per the IBC Section 2902, the required number of plumbing fixture calculations must be determined. The number of new occupants in this addition must be combined with the total number of occupants previously assigned to the existing building that will use this restroom facility. Plumbing fixtures must meet the code requirements for that total number of users. Please indicate those calculations on this sheet, and show calculations for the number of men and women water closets and lavatories required, along with the service sink. 4. Sheet A7.0; Section C: Should the enlarged Section 1/A8.0 be revised? Please verify. 5. Sheet A9.0; Details 1 and 3: Per the IBC Section 1607.14, interior walls that exceed 6 feet in height shall have adequate strength to resist not less than 5 psf horizontal load. On these details, please provide diagonal bracing from the top of the wall to the roof structure above. Please indicate the brace size and spacing, along with the quantity and size of the connectors required at those locations. 6. Sheet A10.0; Interior Elevations 1 (A, B, and C); Interior Elevations 2 (Public Side): Please finish the detail cuts indicated on these elevations. 7. Sheet S1.1A; General Structural Notes (Foundations): Please provide one copy of the geotechnical report for review. 8. General: Please provide written responses to all review comments. |
| 06/28/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size and serial number of the water meter serving this addition, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012. |
| 07/02/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the site civil plan referenced on sheetP1.1. Reference: Section 107.2.1, IBC 2012. 2. Hand sinks (e.g. K-45) cannot be indirectly wasted. Hand sinks must drain to the grease waste system unless the sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Sections 301.3, 802.1, and 1003.3, IPC 2012, as amended by the City of Tucson. 3. Provide justification for sink K-38 and dipperwell K-39 not being directly connected to the grease waste system. Reference: Sections 301.3, 802.1, and 1003.3, IPC 2012, as amended by the City of Tucson. 4. Explain why none of the new bistro plumbing fixtures are draining to the grease waste system. Reference: section 1003.3, IPC 2012 as amended by the City of Tucson. 5. Provide a cleanout at the base of each vertical rainwater conductor that connects to an underground storm drain. Reference: Sections 708.3.4 and 1101.8, IPC 2012. 6. Clarify the note on sheet P1.1 that calls for a 3" ORWL to terminate with a 2"downspout nozzle. The size of a drainage pipe shall not decrease in the direction of flow. Reference: Section 1101.5, IPC 2012 7. Verify the size of the existing gas main (shown as 3.5") and state the total developed pipe length. The question is whether the section of gas main between the meter and the connection of the new 1-1/4" pipe is adequate. Reference: Section 401.3, IFGC 2012. |
| 07/02/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Demonstrate energy code compliance for the addition to the building envelope and the new mechanical system using calculations based on the current code (i.e. provide COMcheck). Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012. 2. Provide heating and cooling load calculations for AC-1, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson. 3. Clarify the outside air requirement for AC-1. On the mechanical floor plan and on the mechanical roof plan it is 300 CFM, on the unit schedule it is 500 CFM; the ventilation calculations call for 425 CFM. 4. Clarify the balancing data for EF-1. Is the exhaust flow rate 1883 CFM or 1900 CFM? 5. Provide protection of the exhaust discharge opening from rain. Reference: Section 501.3.2, IMC 2012. 6. Provide a shaft to enclose the grease duct or provide a field-applied grease duct enclosure. Reference: Section 506.3.11, IMC 2012. 7. Where is detail 5/M4.0? It is called out on sheet M2.0. 8. Verify the size of the round grease duct on the roof entering EF-1. It is 16" on the shop drawings but 20" on the mechanical roof plan. Similarly, the rectangular grease duct is 20" x 12" on sheet M1.0 but is 28" x 8" on sheet M2.0 9. Verify that the evaporative cooling section of the makeup air unit is equipped with a recirculating water system. Reference: Section 928.2, IMC 2012 and ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.gov/viewdocument/?docName=http://www.azleg.gov/ars/45/00313.htm). |
| 07/09/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code, for the exterior lighting. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd . See chapter 104 for plan submittal requirements. #2. Ref; Plan Sheet E2.0. (a) The number of 'A' and 'B' luminaires shown on the lighting floor plans does not correlate with the amount on the Comcheck. Please clarify. (b) Assign a branch circuit and panel designation for the luminaires. NEC 408.4. #3. All 125 volt receptacles in the kitchen and food prep areas, or within 6' of the edge of a sink need to be GFI protected. NEC 210.8b2, b5. #4. Ref; Plan Sheet E7.0. Kitchen equipment # E54 and # E55 are not shown on the Kitchen Equipment Schedule. Please clarify. Ref; 2012 IBC 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code. |
| 07/12/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T18CM04423- New Building Addition - Ref. DP18-0066 Bistro Addition Building Plan Review (1st Review) 210 N. Maguire Avenue - O-3 Zoning TRANSMITTAL DATE: July 12, 2018 DUE DATE: July 17, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the Building Plans for the Bistro addition but cannot approve them at this time. While the building footprint is consistent with the approved version of the DP as it relates to the zoning review purview (Building footprint, Height, square footage that is under review zoning cannot approve the building plans at this time PDSD Commercial Plans reviewers have approved the building plans. 2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. 3. COMMENT: If any changes are necessary, due to the PDSD Commercial Plan Reviewer's comments that affect or change the building footprint, height, or square footage, the DP will need to be updated prior to approval of the building plans by Zoning. 4. COMMENT: Once the plans have been reviewed and approved by the PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Building plans |
| 07/16/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |