Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2018 AVAUGHN1 MECHANICAL-COMMERCIAL REVIEW Needs Review
08/27/2018 AVAUGHN1 ZONING REVIEW Needs Review
08/27/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/27/2018 AVAUGHN1 PLUMBING-COMMERCIAL REVIEW Needs Review
08/27/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 4; Allowable Area Calculations: On Sheet A1.0, per the IBC Table 503, the allowable area per floor for an A-3 occupancy with IIIB construction type is 9500 SF. Please revise the calculation.
2. Previous Comment 9; Special Inspections: Please provide a Special Inspection Certificate with the required special inspections and the ICC certified inspectors that will perform those inspections.