Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T18CM04422
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2018 | AVAUGHN1 | ZONING | REVIEW | Needs Review | |
| 08/27/2018 | AVAUGHN1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/27/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/27/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 4; Allowable Area Calculations: On Sheet A1.0, per the IBC Table 503, the allowable area per floor for an A-3 occupancy with IIIB construction type is 9500 SF. Please revise the calculation. 2. Previous Comment 9; Special Inspections: Please provide a Special Inspection Certificate with the required special inspections and the ICC certified inspectors that will perform those inspections. |
| 08/27/2018 | AVAUGHN1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |