Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM04422
Parcel: 13324010C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM04422
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2018 MARTIN BROWN FIRE REVIEW Approved
06/26/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a natural gas piping design, including the piping layout on a floor plan and a natural gas schematic showing the sizes, loads and developed lengths of the piping. Reference: Section 107.2.1, IBC 2012.
2. Show how the storm drainage from the existing roof will be accommodated (see the roof framing drawing in the structural calculations). Reference: Section 107.2.1, IBC 2012.
06/26/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.
2. Provide heating and cooling load calculations, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson.
3. Verify that the primary roof drain on the south end of the building terminates in an area capable of absorbing the condensate from the AC unit without surface drainage. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
06/26/2018 ROBERT SHERRY WATER REVIEW Completed
06/29/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Specify deferred submittal for roof trusses.
2. Show EXIT lighting on the reverse ceiling plan.
3. The type of construction specified for the addition is Type II-B, which does not allow the use of combustible materials for the roof construction unless it is of fire retardant wood. IBC 603.1
4. Provide allowable area calculations based on a revised construction type as indicated on comment item no. 4. IBC
5. Provide minimum plumbing fixture calculations for verification that existing plumbing fixtures are adequate for the increased occupant load of the fitness room addition. IBC TABLE 2902.1
6. If existing toilet facilities are to be used for the occupants of the addition, they must be located along path of travel not exceeding a distance of 500 ft. Verify location of existing facilities. IBC 2902.3.2
7. A drinking fountain is required for persons in wheelchairs and standing use. In lieu of drinking fountails, a point of use water dispenser may be substituted. The dispenser must be labeled and plumbed from the water distribution piping and located along and accessible route. IBC TABLE 2902.1, COT Policy 2008-21(E)
8. The structural calculations specify masonry lintels ML3 to be used over window type A on the south wall. This lintel type is not shown on the ROOF FRAMING PLAN nor on the MASONRY LINTEL SCHEDULE. Revise and correct. IBC 107.2.1
9. Provide a list of special inspections specific for this project. IBC 1704.2
10. Submit the geotechnical report for this project. IBC 1803.1
07/09/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code, for the exterior lighting. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd . See chapter 104 for plan submittal requirements.
07/11/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM04422- New Building Addition - Ref. DP18-0066
GYM Addition Building Plan Review (1st Review)
8111 E. Broadway Boulevard - O-3 Zoning

TRANSMITTAL DATE: July 11, 2018

DUE DATE: July 17, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the Building Plans for the GYM addition but cannot approve them at this time. While the building footprint is consistent with the approved version of the DP as it relates to the zoning review purview (Building footprint, Height, square footage that is under review zoning cannot approve the building plans at this time PDSD Commercial Plans reviewers have approved the building plans.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.

3. COMMENT: If any changes are necessary, due to the PDSD Commercial Plan Reviewer's comments that affect or change the building footprint, height, or square footage, the DP will need to be updated prior to approval of the building plans by Zoning.

4. COMMENT: Once the plans have been reviewed and approved by the PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Building plans
07/16/2018 LOREN MAKUS ENGINEERING REVIEW Approved