Permit Number: T18CM04357
Parcel: 140420270

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T18CM04357
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Specify access to the mezzanine.
2. Provide structural calculations to support basis of design.
3. Indicate the ceiling height above the mezzanine; 7' min. is required.
4. Indicate guardrails at mezzanine perimeter.
5. Provide floor plan of mezzanine.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2018 QJONES1 APPROVAL SHELF Completed
07/30/2018 QJONES1 OUT TO CUSTOMER Completed
07/30/2018 QJONES1 REJECT SHELF Completed