Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T18CM04357
Parcel: 140420270

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM04357
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2018 EHAMBLI1 ZONING REVIEW Approved
06/05/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. The one line diagrams show 2 - 'MSB 2' Services. Correct to show 'MSB 3'.
#2. The amp ratings of the new service equipment does not seem to correlate with the load calculations. The load calcs for the existing panels are blank. Please provide the load calcs for all equipment downstream of the new 'MSB 3'.
#3. Why are there only panel schedules shown for panels 'C-SE' and 'L-SE' ?
#4. Panel 'CRL' is not shown as being relocated on the demo plan.
Ref 2012 IBC sec 107.2.1, 2011 NEC art 220.
06/05/2018 EHAMBLI1 ENGINEERING REVIEW Passed
06/05/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/05/2018 ROBERT SHERRY WATER REVIEW Completed
06/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/05/2018 MARTIN BROWN FIRE REVIEW Approved
06/05/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed