Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM04357
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/05/2018 | EHAMBLI1 | ZONING | REVIEW | Approved | |
| 06/05/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 06/05/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. The one line diagrams show 2 - 'MSB 2' Services. Correct to show 'MSB 3'. #2. The amp ratings of the new service equipment does not seem to correlate with the load calculations. The load calcs for the existing panels are blank. Please provide the load calcs for all equipment downstream of the new 'MSB 3'. #3. Why are there only panel schedules shown for panels 'C-SE' and 'L-SE' ? #4. Panel 'CRL' is not shown as being relocated on the demo plan. Ref 2012 IBC sec 107.2.1, 2011 NEC art 220. |
| 06/05/2018 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
| 06/05/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/05/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/05/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/05/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/05/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |