Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide load calcs for the existing service and new panel. If the load for the new panel is unknown at this time, please include a note, " loads for future equipment to be determined and permitted by seperate permit". Or equivalent.
Provide AIC ratings for the electrical equipment.
Specify fuse types.
Ref; 2012 IBC sec 107.2.1, 2011 NEC