Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM04266
Parcel: 11202033P

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T18CM04266
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2018 ANY ZONING REVIEW Active
06/01/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show how the outside air is to be introduced into the fan coil unit.
2. Provide heating/cooling load calculations.
3. Provide a sign noting the dryer exhaust vent length.
06/01/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/01/2018 ANY ENGINEERING REVIEW Active
06/01/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Specify the type of occupancy for the apartment.
2. Provide a guardrail detail of the second floor deck.
4. Indicate the size of the existing bedroom egress windows.
06/01/2018 ROBERT SHERRY WATER REVIEW Completed
06/01/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/01/2018 ANY COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
06/04/2018 MARTIN BROWN FIRE REVIEW Reqs Change Per section 3408 of the 2012 IBC, building either needs fire sprinklers or an appeal through the building code official to forego requirement.