Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T18CM04263
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2018 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 10/19/2018 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Reviewer: Chris Anderson MECHANICAL – COMMERCIAL Regarding the ME’s response to previous Mechanical review comment 2, the heat pump schedule and outdoor unit schedule on this sheet were not revised to show the unit(s) that were selected in the heating and cooling load calculations. The ME indicates Carrier heat pumps with a total capacity of 59.0 MBH, while the Goodman selection in the calculations shows a total capacity of 51.6 MBH which is closer to the 46.6 MBH cooling load. Revise the schedules on sheet M-1 to show the Goodman selection with SEER 16. Portions of all the revised mechanical sheets, especially sheet M-1 and engineers’ seals on others, are illegible. Reprint these sheets so that they are clearly legible and resubmit. |
| 10/19/2018 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRICAL – COMMERCIAL The EE’s second response to previous Electrical item 2 includes changes to exterior fixtures F and G so that the selected fixtures have a maximum color temperature of 3500K. However, these changes were not made on the Light Fixture Schedule, sheet E3A. Please revise this schedule. |
| 10/19/2018 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | PLUMBING – COMMERCIAL The ME’s second response to first review Plumbing comment 8 says again, “rain gutter and downspouts sized by Architect..” No calculations requested by the previous reviewer were included in this resubmittal package. The ME must coordinate with Architect to provide this information. Portions of all the revised plumbing sheets, especially engineers’ seals, are illegible. Reprint these sheets so that they are clearly legible and resubmit. |
| 11/02/2018 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD Zoning Review Section PROJECT: T18CM04263 - New Building (DPS - Airplane Hanger) Building Plan Review (3rd Review) AZ D.P.S. 1910 E. Aero Park Boulevard - I-2 Zoning TRANSMITTAL DATE: November 2, 2018 DUE DATE: November 5, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the building plans for compliance with the submitted development package. While the building footprint is consistent with the DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until the PDSD Commercial Plans reviewers have approved the building plans. 2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. (Include a copy as reference of the approved and PDSD stamped version of the DP with the next building plan submittal. 3. 3. COMMENT: If any changes are necessary, due to the PDSD Commercial Plan Reviewer's comments that affect or change the building footprint, height, or square footage, the DP will need to be updated prior to approval of the building plans by Zoning. 4. 4. COMMENT: Once the plans have been reviewed and approved by the 3rd Party and PDSD Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning. If you have any questions about this transmittal, contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: As noted by the zoning comments |
| 11/05/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | T18CM04263 1) Engineering has reviewed the building plans and they are in conformance with the approved DP. Engineering cannot approve the building plans at this time due to outstanding review comments from other departments 2) Engineering can conduct an over the counter review once the above comment has been addressed John Van Winkle, P.E. John.VanWinkle@tucsonaz.gov 520-837-5007 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/19/2018 | SVALENZ1 | OUT TO CUSTOMER | Completed |