Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T18CM04183
Parcel: 12212039C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM04183
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2018 ANDREW CONNOR ZONING REVIEW Approved
05/30/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/30/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide an electrical plan showing the designated branch circuit and panel utilized, disconnecting means, OCPD, for the fan motor. Also show the location of the panel and a complete panel schedule including load calcs.
Ref; 2012 IBC 107.2.1, 2011 NEC art 430.
05/30/2018 ACONNOR1 ENGINEERING REVIEW Passed
05/30/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Passed
05/30/2018 ROBERT SHERRY WATER REVIEW Completed
05/30/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/30/2018 MARTIN BROWN FIRE REVIEW Approved
06/05/2018 LPEREZ2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed