Permit Number: T18CM04072
Parcel: 136290020

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM04072
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2018 JVINCEN1 FIRE REVIEW Approved
06/01/2018 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS
06/15/2018 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Completed
06/22/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
#1. Indicate the wiring methods and or electrical equipment, conduits, U.G. splice boxes, etc. utilized for extending the power for the lighting branch circuit to the new location.
#2. Verify the that if re-aiming of the luminaires is required. The relocated luminaires must comply with section 601.2(2) of the Tucson/Pima County Outdoor Lighting Code.
Ref; 2012 IBC sec 107.2.1, 2011 NEC. Tucson/Pima County Outdoor Lighting Code.
Dan.santacruz@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
06/28/2018 SVALENZ1 APPROVAL SHELF Completed
06/28/2018 SVALENZ1 OUT TO CUSTOMER Approved
06/28/2018 SVALENZ1 REJECT SHELF Completed